Accessories • Cables
142
Automation PC 3100 user's manual V0.60
5.1.1.6 Cable pinout
Warning!
If a field-assembled cable is desired, it must be wired according to this pinout.
If a field-assembled cable is used, B&R cannot make any guarantee as to its functionality. Functionality
is only ensured with cables provided by B&R.
14
20
Pinout per TIA/EIA 568A
White (green)
Green
White (orange)
Blue
White (blue)
Orange
White (brown)
Brown
Shield
Figure 37: 5CASD3.xxxx-00 - Pinout
5.1.1.7 Wiring
The following information and figure apply when using a field-assembled cable that is not directly connected to a
B&R device, but to an RJ45 network interface (e.g. patch panel).
Wiring must meet category 6a (Cat 6a) or category 7 (Cat 7) requirements. Exceeding the maximum total length
of 100 m is not permitted.
B&R device
B&R device
Patch panel
Patch panel
Patch cable
Patch cable
Field-assembled cable
Max. 5 m
Max. 100 m
Max. 5 m
Figure 38: Wiring with a field-assembled cable