Technical data • Complete system
36
Automation PC 3100 user's manual V0.60
2.5.10 LED status indicators
LED status indicators are located on the front of the APC3100.
Power
Disk
Link
Run
The following intervals are used for the LED status indicators:
Block size: 250 ms
Repeat interval: 500 ms, 2 boxes thus represent one interval
LED
Color
Status
Explanation
LED status indicators
On
Power supply OK
The device is started up; the battery state is "BAD".
Green
Blinking
Information:
On
The system is in standby mode (S5: soft-off mode or S4: hiber-
nation/suspend-to-disk mode).
Red
Blinking
The MTCX is running; the battery state is "BAD". The system is in
standby mode (S5: soft-off mode or S4: hibernation/suspend-to-
disk mode).
Faulty or incomplete BIOS, MTCX or I/O FPGA update, battery
state OK, power supply OK
Faulty or incomplete BIOS, MTCX or I/O FPGA update, bat-
tery state OK, standby mode (S5: soft-off mode or S4: hiberna-
tion/suspend-to-disk mode)
Faulty or incomplete BIOS, MTCX or I/O FPGA update, battery
state BAD, power supply OK
Faulty or incomplete BIOS, MTCX or I/O FPGA update, battery
state BAD, standby mode (S5: soft-off mode or S4: hiberna-
tion/suspend-to-disk mode)
Red/Green Blinking
Information:
An update must be performed again.
Power
Yellow
On
Power supply not OK; the system is operated from the UPS.
Disk
Yellow
On
Indicates drive access (HDD, SSD, CFast)
On
Indicates an active SDL connection on the male panel connec-
tor.
An active SDL connection was interrupted by a loss of power
to the display unit.
Link
Yellow
Blinking
Information:
The power supply / power connection of the con-
nected display unit must be checked.
Green
Blinking
Automation Runtime is starting up.
This is controlled by Automation Runtime (ARemb and ARwin).
Green
On
Application running
This is controlled by Automation Runtime (ARemb and ARwin).
Red
On
Application in service mode
This is controlled by Automation Runtime (ARemb and ARwin).
Run
Orange
Blinking
A license violation exists.
Table 26: LED status indicators - Data