APPENDIX E. COMMUNICATIONS
HF-2500A HIGH FREQUENCY WELD CONTROL
990-371
E-7
Command
COPY {from_schedule_number} {to_schedule_number}
<crlf><lf>
Control State
Any
Description
Allows one schedule to be copied to another schedule number. From_schedule_number and
to_schedule_number may be any number from 0 to 99. Copying a schedule to itself has no
effect other than to invoke a schedule printout when "PRINT SCHEDULES/PROGRAMS" is
enabled.
Command
SCHEDULE
<crlf><lf>
Control State
Any state
except
while welding.
Description
Requests the Power Supply to return the currently selected schedule number.
Command
SCHEDULE {READ | SET}
<crlf>
[
parameter_name value
<crlf>]
<lf>
Control State
RUN state.
Description
Provides control over the Power Supply schedule parameters. When used with the "READ"
keyword, all parameters pertaining to the currently loaded schedule are returned (see
SCHEDULE under Power Supply Originated Commands). When the "SET" keyword is used,
the host may set (change) the value of one or more of the parameters pertaining to the currently
loaded schedule. The following is a list of valid literal substitutions for the parameter_name
and value variables:
ENG1
FEEDBACK1
ENG2
FEEDBACK 2
SQUEEZE
UP1
WELD1
DOWN1
COOL
UP2
WELD2
DOWN2
HOLD
RINDEX1
RINDEX2
EINDEX1
EINDEX2
{ weld_energy }
energy amount for pulse 1
{ KA | V | KW}
feedback type for pulse 1
{ weld_energy }
energy amount for pulse 2
{ KA | V | KW}
feedback type for pulse 2
{ squeeze_time }
squeeze time
{ weld_time }
up slope time of pulse 1
{ weld_time }
weld time of pulse 1
{ weld_time }
down slope time of pulse 1
{ weld_time }
cool time
{ weld_time }
up slope time of pulse 2
{ weld_time }
weld time of pulse 2
{ weld_time }
down slope time of pulse 2
{ hold_time }
hold time
{
resistance index
} index value into PID resistance table for pulse 1
{
resistance index
} index value into PID resistance table for pulse 2
{
energy index
} index value into PID energy table for pulse 1
{
energy index
} index value into PID energy table for pulse 2
NOTES:
squeeze_time
and
hold_time
are the parameter that defines the time for the given period in 1
msec. Valid range is from 0 to 999.
weld_time
is the parameter that defines the time for the given period. . Each count of
weld_
time
is equivalent to 0.01 for increments from 0.1 to 0.99 ms and increments of 0.1 ms for 1.0
to 9.9 ms and increments of 1.0 ms for 10.0 to 99.0 ms. (see table next page)