Setting of the voltage difference between the line voltage and the bus voltage. The difference
is set depending on the network configuration and expected voltages in the two networks
running asynchronously. A normal setting is 0.10-0.15 p.u.
FreqDiffMin
The setting
FreqDiffMin is the minimum frequency difference where the systems are defined
to be asynchronous. For frequency differences lower than this value, the systems are
considered to be in parallel. A typical value for
FreqDiffMin is 10 mHz. Generally, the value
should be low if both synchronizing and synchrocheck functions are provided, and it is better
to let the synchronizing function close, as it will close at exactly the right instance if the
networks run with a frequency difference.
To avoid overlapping of the synchronizing function and the synchrocheck
function the setting
FreqDiffMin must be set to a higher value than used
setting
FreqDiffM, respective FreqDiffA used for synchrocheck.
FreqDiffMax
The setting
FreqDiffMax is the maximum slip frequency at which synchronizing is accepted. 1/
FreqDiffMax shows the time for the vector to move 360 degrees, one turn on the
synchronoscope, and is called Beat time. A typical value for
FreqDiffMax is 200-250 mHz, which
gives beat times on 4-5 seconds. Higher values should be avoided as the two networks
normally are regulated to nominal frequency independent of each other, so the frequency
difference shall be small.
FreqRateChange
The maximum allowed rate of change for the frequency.
tBreaker
The
tBreaker shall be set to match the closing time for the circuit breaker and should also
include the possible auxiliary relays in the closing circuit. It is important to check that no slow
logic components are used in the configuration of the IED as there then can be big variations
in closing time due to those components. Typical setting is 80-150 ms depending on the
breaker closing time.
tClosePulse
The setting for the duration of the breaker close pulse.
tMaxSynch
The setting
tMaxSynch is set to reset the operation of the synchronizing function if the
operation does not take place within this time. The setting must allow for the setting of
FreqDiffMin, which will decide how long it will take maximum to reach phase equality. At the
setting of 10 mHz, the beat time is 100 seconds and the setting would thus need to be at least
tMinSynch plus 100 seconds. If the network frequencies are expected to be outside the limits
from the start, a margin needs to be added. A typical setting is 600 seconds.
tMinSynch
The setting
tMinSynch is set to limit the minimum time at which the synchronizing closing
attempt is given. The synchronizing function will not give a closing command within this time,
from when the synchronizing is started, even if a synchronizing condition is fulfilled. A typical
setting is 200 ms.
Section 14
1MRK 505 343-UEN B
Control
530
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...