![background image](http://html1.mh-extra.com/html/abb/relion-670-series/relion-670-series_applications-manual_3052129087.webp)
3
3
Ph Ph
Ph E
U
Uo
U
-
-
=
=
EQUATION1926 V1 EN-US
(Equation 7)
The primary rated voltage of such VT is always equal to UPh-E Therefore, three series
connected VT secondary windings will give the secondary voltage equal only to one individual
VT secondary winding rating. Thus the secondary windings of such open delta VTs quite often
has a secondary rated voltage close to rated phase-to-phase VT secondary voltage, that is,
115V or 115/√3V as in this particular example. Figure
gives an overview of the actions which
are needed to make this measurement available to the built-in protection and control
functions within the IED.
1
L1
IED
L2
L3
138
3
115
3
kV
V
+3Uo
138
3
115
3
kV
V
138
3
115
3
kV
V
IEC06000602-4-en.vsdx
# Not Used
# Not Used
# Not Used
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AI N
2
3
4
5
IEC06000602 V4 EN-US
Figure 23: Open delta connected VT in low impedance or solidly earthed power system
1MRK 505 343-UEN B
Section 4
Analog inputs
81
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...