6.1.3
Connection examples for high impedance differential
protection
GUID-8C58A73D-7C2E-4BE5-AB87-B4C93FB7D62B v5
WARNING! USE EXTREME CAUTION! Dangerously high voltages might be
present on this equipment, especially on the plate with resistors. De-energize
the primary object protected with this equipment before connecting or
disconnecting wiring or performing any maintenance. The plate with resistors
should be provided with a protective cover, mounted in a separate box or in a
locked cubicle. National law and standards shall be followed.
6.1.3.1
Connections for three-phase high impedance differential protection
GUID-C12CCAAF-5AE5-4A9C-AC9C-F56A66FD2C14 v8
Generator, reactor or busbar differential protection is a typical application for three-phase
high impedance differential protection. Typical CT connections for three-phase high
impedance differential protection scheme are shown in figure
L1
(A)
L2
(B)
L3
(C)
Protected Object
CT 1200/1
Star/Wye
Connected
L1
(A)
L2
(B)
L3
(C)
CT 1200/1
Star/Wye
Connected
7
8
9
1
01
11
2
1
2
3
4
5
6
AI01
(I)
AI02
(I)
AI03
(I)
AI04
(I)
AI05
(I)
AI06
(I)
7
6
X1
R
4
R
5
R
6
1
2
1
2
1
2
11
12
13
14
U
U
U
R
1
1
3
4
2
1
3
R
2
2
4
1
3
R
3
2
4
1
2
3
4
5
6 7
L1 (A)
L2 (B)
L3 (C)
N
3-Ph Plate with Metrosils and Resistors
2
3
5
4
X
X
L1 (A)
L2 (B)
L3 (C)
N
1
IED
IEC07000193_4_en.vsd
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
TYPE
IEC07000193 V4 EN-US
Figure 34: CT connections for high impedance differential protection
Pos
Description
1
Scheme earthing point
It is important to insure that only one earthing point exist in this scheme.
2
Three-phase plate with setting resistors and metrosils. Protective earth is a separate 4 mm screw
terminal on the plate.
3
Necessary connection for three-phase metrosil set.
4
Position of optional test switch for secondary injection into the high impedance differential IED.
1MRK 505 343-UEN B
Section 6
Differential protection
99
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...