there are two autoreclosers and two synchronism check devices with a priority circuit to allow
one to close first.
The differential protection for up to 6 CT sets, 3–5 line ends is the main protection function. It
is available with communication modules for single or redundant channels and can be used in
two- or multi-terminal arrangements.
Measuring functions for S, P, Q, I, U, PF, f are available for local presentation on the local HMI
and/or remote presentation. The availability of additional analog inputs allows connection of
separate metering cores and a calibration parameter on the measurement function allows
calibration at site to very high accuracy.
Optional functions can be ordered and include functions such as full control, local and remote,
directional earth fault, out-of-step protection, frequency protection, and so on. These optional
functions must be added to the configuration and loaded into the IED after delivery.
The following should be noted. The configuration is made with the binary input and binary
output boards in the basic IED delivery. In many cases this is sufficient, in other cases, for
example with full control of all apparatuses included more IO cards are required. Our proposal
for a full version with control is to use two binary input modules and two binary output
modules. For systems without substation automation, a second binary output board might be
required.
Section 3
1MRK 505 343-UEN B
Configuration
56
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...