19.2.2
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV
SEMOD173197-1 v2
PID-415-SETTINGS v5
Table 56: GOOSEINTLKRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
19.2.3
Setting guidelines
SEMOD55317-5 v6
There are two settings related to the IEC 61850–8–1 protocol:
Operation User can set IEC 61850 communication to On or Off.
GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send and received.
19.2.4
Generic communication function for Single Point indication
SPGAPC, SP16GAPC
SEMOD55999-1 v4
19.2.4.1
Application
SEMOD55350-5 v6
Generic communication function for Measured Value (SPGAPC) function is used to send one
single logical output to other systems or equipment in the substation. It has one visible input,
that should be connected in ACT tool.
19.2.4.2
Setting guidelines
SEMOD55376-5 v4
There are no settings available for the user for SPGAPC. However, PCM600 must be used to get
the signals sent by SPGAPC.
19.2.5
Generic communication function for Measured Value MVGAPC
SEMOD55402-1 v3
19.2.5.1
Application
SEMOD55872-5 v9
Generic communication function for Measured Value MVGAPC function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It
can also be used inside the same IED, to attach a RANGE aspect to an analog value and to
permit measurement supervision on that value.
19.2.5.2
Setting guidelines
SEMOD55424-5 v5
The settings available for Generic communication function for Measured Value (MVGAPC)
function allows the user to choose a deadband and a zero deadband for the monitored signal.
Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and low-
low ranges of the measured value. The actual range of the measured value is shown on the
range output of MVGAPC function block. When a Measured value expander block (RANGE_XP)
1MRK 505 343-UEN B
Section 19
Station communication
683
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...