Busbar
Protection
Busbar
1
2
2
1
en06000196.vsd
IED
1
IEC06000196 V2 EN-US
Figure 11: Example how to set CTStarPoint parameters in the IED
For busbar protection it is possible to set the
CTStarPoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT inputs
marked with 1 in figure
CTStarPoint = ToObject, and for all CT inputs marked with 2 in
, set
CTStarPoint = FromObject.
The second solution will be to use all connected bays as reference objects. In that case for all
CT inputs marked with 1 in figure
, set
CTStarPoint = FromObject, and for all CT inputs
marked with 2 in figure
CTStarPoint = ToObject.
Regardless which one of the above two options is selected busbar differential protection will
behave correctly.
The main CT ratios must also be set. This is done by setting the two parameters
CTsec and
CTprim for each current channel. For a 1000/1 A CT the following setting shall be used:
•
CTprim = 1000 (value in A)
•
CTsec =1 (value in A).
1MRK 505 343-UEN B
Section 4
Analog inputs
65
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...