Figure 412: Example of a station configuration with the IED receiving analog values from
both classical measuring transformers and merging units.
19.3.2
Setting guidelines
GUID-29B296B3-6185-459F-B06F-8E7F0C6C9460 v4
Merging Units (MUs) have several settings on local HMI under:
•
Main menu/Configuration/Analog modules/MUx:92xx. The corresponding settings are
also available in PST (PCM600).
•
Main menu/Configuration/Communication/Merging units configuration/MUx:92xx. The
corresponding settings are also available in ECT (PCM600).
XX can take value 01–12.