Definite time delay for both steps
3.
Two overvoltage steps with the following built-in features
•
Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for both steps
4. Two undervoltage steps with the following built-in features
•
Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for both steps
All these four protection elements within one general protection function works independently
from each other and they can be individually enabled or disabled. However it shall be once
more noted that all these four protection elements measure one selected current quantity and
one selected voltage quantity (see table
). It is possible to simultaneously use
all four-protection elements and their individual stages. Sometimes in order to obtain desired
application functionality it is necessary to provide interaction between two or more protection
elements/stages within one CVGAPC function by appropriate IED configuration (for example,
dead machine protection for generators).
11.1.2.1
Current and voltage selection for CVGAPC function
SEMOD53443-6 v3
CVGAPC function is always connected to three-phase current and three-phase voltage input in
the configuration tool, but it will always measure only the single current and the single voltage
quantity selected by the end user in the setting tool (selected current quantity and selected
voltage quantity).
The user can select, by a setting parameter
CurrentInput, to measure one of the following
current quantities shown in table
.
Table 42: Available selection for current quantity within CVGAPC function
Set value for parameter
"CurrentInput”
Comment
1
phase1
CVGAPC function will measure the phase L1 current phasor
2
phase2
CVGAPC function will measure the phase L2 current phasor
3
phase3
CVGAPC function will measure the phase L3 current phasor
4
PosSeq
CVGAPC function will measure internally calculated positive sequence
current phasor
5
NegSeq
CVGAPC function will measure internally calculated negative sequence
current phasor
6
3 · ZeroSeq
CVGAPC function will measure internally calculated zero sequence current
phasor multiplied by factor 3
7
MaxPh
CVGAPC function will measure current phasor of the phase with
maximum magnitude
8
MinPh
CVGAPC function will measure current phasor of the phase with minimum
magnitude
9
UnbalancePh
CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the
current phasor of the phase with maximum magnitude and current
phasor of the phase with minimum magnitude. Phase angle will be set to
0° all the time
10
phase1-phase2
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase L1 current phasor and phase L2
current phasor (IL1-IL2)
11
phase2-phase3
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase L2 current phasor and phase L3
current phasor (IL2-IL3)
Table continues on next page
Section 11
1MRK 505 343-UEN B
Multipurpose protection
494
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...