Section 6
Differential protection
6.1
High impedance differential protection, single phase
HZPDIF
IP14239-1 v4
6.1.1
Identification
M14813-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
High impedance differential
protection, single phase
HZPDIF
Id
SYMBOL-CC V2 EN-US
87
6.1.2
Application
IP14944-1 v3
SEMOD54734-4 v8
The 1Ph High impedance differential protection function HZPDIF can be used as:
•
Generator differential protection
•
Reactor differential protection
•
Busbar differential protection
•
Autotransformer differential protection (for common and serial windings only)
•
T-feeder differential protection
•
Capacitor differential protection
•
Restricted earth fault protection for transformer, generator and shunt reactor windings
•
Restricted earth fault protection
The application is dependent on the primary system arrangements and location of breakers,
available CT cores and so on.
1MRK 505 343-UEN B
Section 6
Differential protection
93
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...