7.9.3.5
Setting of zones for parallel line application
SEMOD55087-50 v2
Parallel line in service – Setting of zone 1
GUID-F10BF2FF-7B0F-40B0-877B-081E1D5B067B v1
, the zone reach can be set to 85% of
protected line.
However, influence of mutual impedance has to be taken into account.
Parallel line in service – setting of zone 2
GUID-8EAD617A-D33B-453C-83FC-21E3CFC37CB1 v1
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit in all
cases. The greatest reduction of a reach occurs in cases when both parallel circuits are in
service with a single phase-to-earth fault located at the end of a protected line. The equivalent
zero sequence impedance circuit for this case is equal to the one in figure
The components of the zero sequence impedance for the overreaching zones must be equal to
at least:
R
0E
R
0
R
m0
+
=
EQUATION553 V1 EN-US
(Equation 274)
X
0E
X
0
X
m0
+
=
EQUATION554 V1 EN-US
(Equation 275)
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1
0
m
f
Z
K
Z
Z
R
= -
×
+
+
EQUATION1426 V1 EN-US
(Equation 276)
If the denominator in equation
is called B and Z0m is simplified to X0m, then the real and
imaginary part of the reach reduction factor for the overreaching zones can be written as:
( )
( )
( )
( )
2
2
0
Re
Re
0
1
Re
Im
X m
B
K
B
B
×
= -
+
EQUATION1427 V2 EN-US
(Equation 277)
( )
( )
( )
( )
2
2
0
Im
Im
0
Re
Im
X m
B
K
B
B
×
=
+
EQUATION1428 V2 EN-US
(Equation 278)
Parallel line is out of service and earthed in both ends
GUID-AEF4E5D3-A486-4DC7-8B95-83AADE67F966 v1
Apply the same measures as in the case with a single set of setting parameters. This means
that an underreaching zone must not overreach the end of a protected circuit for the single
phase-to-earth faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance) equal to:
1MRK 505 343-UEN B
Section 7
Impedance protection
281
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...