Table 41: Settings
U/f op (%)
Timer
Time set (s)
105
t1
7200 (max)
112
t2
600
119
t3
60
126
t4
20
133
t5
8
140
t6
4
Information on the cooling time constant T
cool
should be retrieved from the power
transformer manufacturer.
1
2
5
50
200
110
120
130
140
150
100
0.05
0.1
0.2
0.5
10
20
100
V/Hz
%
Continous
Time
(minutes)
t6
t5
t4
t3
t2
t1
transformer capability curve
relay operate characteristic
en01000377.vsd
IEC01000377 V1 EN-US
Figure 302: Example on overexcitation capability curve and V/Hz protection settings for
power transformer
9.5
Voltage differential protection VDCPTOV
SEMOD153860-1 v2
9.5.1
Identification
SEMOD167723-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage differential protection
VDCPTOV
-
60
Section 9
1MRK 505 343-UEN B
Voltage protection
482
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...