![background image](http://html1.mh-extra.com/html/abb/relion-670-series/relion-670-series_applications-manual_3052129510.webp)
11.1.3.5
Voltage restrained overcurrent protection for generator and step-up
transformer
M13088-158 v3
Example will be given how to use one CVGAPC function to provide voltage restrained
overcurrent protection for a generator. Let us assume that the time coordination study gives
the following required settings:
•
Inverse Time Over Current TOC/IDMT curve: ANSI very inverse
•
Pickup current of 185% of generator rated current at rated generator voltage
•
Pickup current 25% of the original pickup current value for generator voltages below 25%
of rated voltage
This functionality can be achieved by using one CVGAPC function. The following shall be done
in order to insure proper operation of the function:
1.
Connect three-phase generator currents and voltages to one CVGAPC instance (for
example, GF05)
2.
Set
CurrentInput to value MaxPh
3.
Set
VoltageInput to value MinPh-Ph (it is assumed that minimum phase-to-phase voltage
shall be used for restraining. Alternatively, positive sequence voltage can be used for
restraining by selecting
PosSeq for this setting parameter)
4. Set base current value to the rated generator current primary amperes
5. Set base voltage value to the rated generator phase-to-phase voltage in kV
6. Enable one overcurrent step (for example, OC1)
7.
Select
CurveType_OC1 to value ANSI Very inv
8. If required set minimum operating time for this curve by using parameter
tMin_OC1
(default value 0.05s)
9. Set
StartCurr_OC1 to value 185%
10. Set
VCntrlMode_OC1 to On
11. Set
VDepMode_OC1 to Slope
12. Set
VDepFact_OC1 to value 0.25
13. Set
UHighLimit_OC1 to value 100%
14. Set
ULowLimit_OC1 to value 25%
Proper operation of the CVGAPC function made in this way can easily be verified by secondary
injection. All other settings can be left at the default values. Furthermore the other built-in
protection elements can be used for other protection and alarming purposes.
11.1.3.6
Loss of excitation protection for a generator
M13088-182 v3
Example will be given how by using positive sequence directional overcurrent protection
element within a CVGAPC function, loss of excitation protection for a generator can be
achieved. Let us assume that from rated generator data the following values are calculated:
•
Maximum generator capability to contentiously absorb reactive power at zero active
loading 38% of the generator MVA rating
•
Generator pull-out angle 84 degrees
This functionality can be achieved by using one CVGAPC function. The following shall be done
in order to insure proper operation of the function:
1.
Connect three-phase generator currents and three-phase generator voltages to one
CVGAPC instance (for example, GF02)
2.
Set parameter
CurrentInput to PosSeq
3.
Set parameter
VoltageInput to PosSeq
4. Set base current value to the rated generator current primary amperes
5. Set base voltage value to the rated generator phase-to-phase voltage in kV
6. Set parameter
RCADir to value -84 degree (that is, current lead voltage for this angle)
Section 11
1MRK 505 343-UEN B
Multipurpose protection
504
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...