IEC07000198 V3 EN-US
Figure 427: Configuration for using an instance in task time group 1 as DFT reference
Assume instance SMAI7:7 in task time group 1 has been selected in the configuration to control
the frequency tracking . Observe that the selected reference instance (i.e. frequency tracking
master) must be a voltage type. Observe that positive sequence voltage is used for the
frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
SMAI1:1:
DFTRefExtOut = DFTRefGrp7 to route SMAI7:7 reference to the SPFCOUT output,
DFTReference = DFTRefGrp7 for SMAI1:1 to use SMAI7:7 as reference (see Figure
) SMAI2:2 –
SMAI12:12:
DFTReference = DFTRefGrp7 for SMAI2:2 – SMAI12:12 to use SMAI7:7 as reference.
For task time group 2 this gives the following settings:
SMAI1:13 – SMAI12:24:
DFTReference = ExternalDFTRef to use DFTSPFC input of SMAI1:13 as
reference (SMAI7:7)
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
DFTReference = ExternalDFTRef to use DFTSPFC input as reference
(SMAI7:7)
Example 2
Section 22
1MRK 505 343-UEN B
Basic IED functions
726
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...