k max sr
R
al
alreq
ct
L
2
pr
r
I
I
S
E
E
a R
R
I
I
×
æ
ö
³
=
× ×
+
+
ç
÷
è
ø
EQUATION1080 V2 EN-US
(Equation 566)
kzone1 sr
R
al
alreq
ct
L
2
pr
r
I
I
S
E
E
k R
R
I
I
×
æ
ö
³
=
× ×
+
+
ç
÷
è
ø
EQUATION1081 V2 EN-US
(Equation 567)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and
reverse faults (A)
I
kzone1
Maximum primary fundamental frequency current for faults at the end of
zone 1 reach (A)
I
pr
The rated primary CT current (A)
I
sr
The rated secondary CT current (A)
I
r
The rated current of the protection IED (A)
R
ct
The secondary resistance of the CT (
W
)
R
L
The resistance of the secondary wire and additional load (
W
). In solidly
earthed systems the loop resistance containing the phase and neutral
wires should be used for phase-to-earth faults and the resistance of the
phase wire should be used for three-phase faults.
In isolated or high impedance earthed systems the resistance of the single
secondary wire can always be used.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for
I
r
=1 A and S
R
=0.150 VA/channel for I
r
=5 A
a
This factor depends on the design of the protection function and can be a
function of the primary DC time constant of the close-in fault current.
k
This factor depends on the design of the protection function and can be a
function of the primary DC time constant of the fault current for a fault at
the set reach of zone 1.
The a- and k-factors have the following values for the different types of
distance function:
High speed distance: (ZMFPDIS and ZMFCPDIS)
Quadrilateral characteristic:
a = 1 for primary time constant Tp
£
400 ms
k = 3 for primary time constant Tp
£
200 ms
Mho characteristic:
a = 2 for primary time constant Tp
£
400 ms (For a = 1 the delay in
operation due to saturation is still under 1.5 cycles)
k = 3 for primary time constant Tp
£
200 ms
Quadrilateral distance: (ZMQPDIS, ZMQAPDIS and ZMCPDIS, ZMCAPDIS
and ZMMPDIS, ZMMAPDIS)
a = 1 for primary time constant Tp
£
100 ms
a = 3 for primary time constant Tp
>
100 and
£
400 ms
k = 4 for primary time constant Tp
£
50 ms
k = 5 for primary time constant Tp
>
50 and
£
150 ms
Mho distance: (ZMHPDIS)
a = 1 for primary time constant Tp
£
100 ms
a = 3 for primary time constant Tp
>
100 and
£
400 ms
k = 4 for primary time constant Tp
£
40 ms
k = 5 for primary time constant Tp
>
40 and
£
150 ms
1MRK 505 343-UEN B
Section 23
Requirements
737
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...