110kV Busbar
200/1
35 / 0,1
kV
35kV Busbar
500/5
P
Q
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
U
L1L2
IEC09000040-1-en.vsd
IED
IEC09000040-1-EN V1 EN-US
Figure 399: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure
do the following:
1.
Set correctly all CT and VT and phase angle reference channel
PhaseAngleRef (see section
""
) data using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to LV side CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following
table
:
Section 17
1MRK 505 343-UEN B
Monitoring
658
Application manual