Measurement function application for a 110kV OHL
SEMOD54481-12 v9
Single line diagram for this application is given in figure
:
110kV Busbar
110kV OHL
P
Q
600/1 A
110 0,1
/
3
3
kV
IEC09000039-2-en.vsd
IED
IEC09000039-1-EN V2 EN-US
Figure 398: Single line diagram for 110kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated in
figure
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel
PhaseAngleRef (see
section
""
) using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
•
general settings as shown in table
•
level supervision of active power as shown in table
•
calibration parameters as shown in table
Table 51: General settings parameters for the Measurement function
Setting
Short Description
Selected
value
Comments
Operation
Operation Off/On
On
Function must be
On
PowAmpFact
Amplitude factor to scale
power calculations
1.000
It can be used during commissioning to
achieve higher measurement accuracy.
Typically no scaling is required
PowAngComp
Angle compensation for phase
shift between measured I & U
0.0
It can be used during commissioning to
achieve higher measurement accuracy.
Typically no angle compensation is required.
As well here required direction of P & Q
measurement is towards protected object (as
per IED internal default direction)
Mode
Selection of measured current
and voltage
L1, L2, L3
All three phase-to-earth VT inputs are
available
k
Low pass filter coefficient for
power measurement, U and I
0.00
Typically no additional filtering is required
UGenZeroDb
Zero point clamping in % of
Ubase
25
Set minimum voltage level to 25%. Voltage
below 25% will force S, P and Q to zero.
IGenZeroDb
Zero point clamping in % of
Ibase
3
Set minimum current level to 3%. Current
below 3% will force S, P and Q to zero.
UBase (set in
Global base)
Base setting for voltage level
in kV
400.00
Set rated OHL phase-to-phase voltage
IBase (set in
Global base)
Base setting for current level
in A
800
Set rated primary CT current used for OHL
Section 17
1MRK 505 343-UEN B
Monitoring
656
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...