15.1.3.3
Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
On
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
15.1.3.4
Permissive overreaching scheme
M13869-34 v4
Set
Operation
=
On
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
15.1.3.5
Unblocking scheme
M13869-43 v4
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
Set
tSecurity
= 0.035 s
15.1.3.6
Intertrip scheme
M13869-62 v4
Set
Operation
=
On
Set
SchemeType
=
Intertrip
Set
tCoord
50 ms (10 ms + maximal transmission time)
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Off
Set
tSecurity
= 0.015 s
15.2
Phase segregated scheme communication logic for
distance protection ZC1PPSCH
SEMOD141690-1 v2
15.2.1
Identification
SEMOD141699-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase segregated Scheme
communication logic for distance
protection
ZC1PPSCH
-
85
1MRK 505 343-UEN B
Section 15
Scheme communication
605
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...