220kV Busbar
300/1
15 / 0,1
kV
4000/5
100 MVA
242/15,65 kV
Yd5
U
L1L2
, U
L2L3
G
P
Q
100MVA
15,65kV
IEC09000041-1-en.vsd
IED
IEC09000041-1-EN V1 EN-US
Figure 400: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure
do the following:
1.
Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef(see
section
""
) using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following
table:
Section 17
1MRK 505 343-UEN B
Monitoring
660
Application manual