At a setting somewhat longer than the auto-reclosing open time, this facility will not influence
the reclosing. A typical setting of
tTrip could be close to the auto-reclosing open time.
tInhibit, Inhibit resetting delay
A typical setting is
tInhibit = 5.0 s to ensure reliable interruption and temporary blocking of the
function. Function will be blocked during this time after the
tinhibit has been activated.
tReclaim, Reclaim time
The Reclaim time sets the time for resetting the function to its original state, after which a line
fault and tripping will be treated as an independent new case with a new reclosing cycle. One
may consider a nominal CB duty cycle of for instance, O-0.3sec CO- 3 min. – CO. However the 3
minute (180 s) recovery time is usually not critical as fault levels are mostly lower than rated
value and the risk of a new fault within a short time is negligible. A typical time may be
tReclaim = 60 or 180 s dependent of the fault level and breaker duty cycle.
StartByCBOpen
The normal setting is
Off. It is used when the function is started by protection trip signals. If
set
On the start of the autorecloser is controlled by an CB auxiliary contact.
FollowCB
The usual setting is
Follow CB = Off. The setting On can be used for delayed reclosing with
long delay, to cover the case when a CB is being manually closed during the “auto-reclosing
open time” before the auto-reclosing function has issued its CB closing command.
tCBClosedMin
A typical setting is 5.0 s. If the CB has not been closed for at least this minimum time, a
reclosing start will not be accepted.
CBAuxContType, CB auxiliary contact type
It shall be set to correspond to the CB auxiliary contact used. A
NormOpen contact is
recommended in order to generate a positive signal when the CB is in the closed position.
CBReadyType, Type of CB ready signal connected
The selection depends on the type of performance available from the CB operating gear. At
setting
OCO (CB ready for an Open – Close – Open cycle), the condition is checked only at the
start of the reclosing cycle. The signal will disappear after tripping, but the CB will still be able
to perform the C-O sequence. For the selection
CO (CB ready for a Close – Open cycle) the
condition is also checked after the set auto-reclosing dead time. This selection has a value first
of all at multi-shot reclosing to ensure that the CB is ready for a C-O sequence at shot 2 and
further shots. During single-shot reclosing, the
OCO selection can be used. A breaker shall
according to its duty cycle always have storing energy for a CO operation after the first trip.
(IEC 56 duty cycle is O-0.3sec CO-3minCO).
tPulse, Breaker closing command pulse duration
The pulse should be long enough to ensure reliable operation of the CB. A typical setting may
be
tPulse=200 ms. A longer pulse setting may facilitate dynamic indication at testing, for
example, in “Debug” mode of Application Configuration tool (ACT). In CBs without anti-
pumping relays, the setting
CutPulse = On can be used to avoid repeated closing operation
when reclosing onto a fault. A new start will then cut the ongoing pulse.
BlockByUnsucCl
Setting of whether an unsuccessful auto-reclose attempt shall set the Auto-Reclose in block. If
used the inputs BLOCKOFF must be configured to unblock the function after an unsuccessful
Reclosing attempt. Normal setting is
Off.
1MRK 505 343-UEN B
Section 14
Control
549
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...