![background image](http://html1.mh-extra.com/html/abb/relion-670-series/relion-670-series_applications-manual_3052129130.webp)
6.3.3.2
Percentage restrained differential operation
M12541-104 v4
Line differential protection is phase-segregated where the operate current is the vector sum
of all measured currents taken separately for each phase. The restrain current, on the other
hand, is considered the greatest phase current in any line end and it is common for all three
phases. Observe that the protection may no more be phase-segregated when there is an in-
line power transformer included in the protected circuit. These are usually of the Dy or Yd type
and the three phases are related in a complicated way. For example, a single-phase earth fault
on the wye side of the power transformer is seen as a two-phase fault on the delta side of the
transformer.
Operation: Line differential protection function is switched on or off with this setting. If the
parameter
Operation is set to Off this IED is switched over to Slave mode and trip is initiated
by the remote end IED.
The characteristic of the restrained differential function is shown in Figure
characteristic is defined by the settings:
1.
IdMin
2.
EndSection1
3.
EndSection2
4.
SlopeSection2
5.
SlopeSection3
Section 6
1MRK 505 343-UEN B
Differential protection
124
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...