![background image](http://html1.mh-extra.com/html/abb/acs800-07-0610-3/acs800-07-0610-3_hardware-manual_3428312042.webp)
Hardware description
36
Type code
The type code of the drive is indicated on the type designation label, attached on the
supply cubicle door. The type code contains information on the specifications and
configuration of the drive. The first digits from left express the basic configuration
(e.g. ACS800-07-0610-3). The optional selections are given thereafter, separated by
+ signs (e.g. +E202). The main selections are described below.
Note:
The information below is for quick reference only and does not contain all
conditions and details. For more information, refer to
ACS800 Ordering Information
(code: 64556568), available through ABB representatives.
Selection
Alternatives
Product series
ACS800 product series
Type
07
= cabinet-mounted
When no options are selected: IP21 (UL Type 1), main switch/
disconnector(s), 230 V auxiliary voltage, du/dt filtering (+E205), common
mode filtering (CMF) (+E208), EMC/RFI filtering for second environment
(+E210), Standard Application Program, bottom entry/exit of cables,
coated circuit boards, set of English manuals.
Size
Refer to
Technical data:
Ratings
.
Voltage range
(nominal rating in
bold
)
3
= 380/
400
/415 VAC
5
= 380/400/415/440/460/480/
500
VAC
7
= 525/575/600/
690
VAC
+ options
I/O options
Refer to
ACS800 Ordering Information
(3AFY64556568 [English]).
Fieldbus adapter
Application program
Degree of protection
B053
= IP22 (UL Type 1)
B054
= IP42 (UL Type 1)
B055
= IP54 (UL Type 12) (Not available with +C134)
B059
= IP54R (with connection to air outlet duct)
Construction
C121
= Marine construction (reinforced mechanical parts and fastening,
marking of conductors [A1], door handles, self-extinctive materials)
C129
= UL Listed (115 V AC auxiliary voltage, cable conduit entries, all
components UL listed/recognized, max. supply voltage 600 V; +F253,
+F260 and top entry of cables are standard)
C134
= CSA Approved (as +C129, with CSA approved components)
Filters
E202
= EMC/RFI filtering for first environment TN (grounded) system,
restricted (A-limits). Only for 6-pulse ACS800-07-0610-3 and -0760-5.
ReF253 and +F260.
E206
= Sine output filters (Not available with +C121, +C129 or +C134)
Note:
du/dt filtering (+E205), common mode filtering (CMF) (+E208), and
EMC/RFI filtering for second environment (+E210) are standard
equipment.
Resistor braking
D150
= brake choppers
D151
= brake resistors (not available in IP54 or IP54R)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for ACS800-07-0610-3
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 7: ...Update Notice 3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Update Notice 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...