Technical data
127
Materials
Cabinet
Hot-dip zinc-coated (thickness approx. 20 µm) steel sheet (thickness 1.5 mm) with
polyester thermosetting powder coating (thickness approx. 80 µm) on visible surfaces
except back panel. Colour: RAL 7035 (light beige, semigloss).
Busbars
Tin- or silver-plated copper
Fire safety of materials
(IEC 60332-1)
Insulating materials and non-metallic items: Mostly self-extinctive
Packaging
Frame: Wood or plywood. Plastic wrapping: PE-LD. Bands: PP or steel.
Disposal
The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
printed circuit boards contain lead, both of which are classified as hazardous waste within
the EU. They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions,
please contact your local ABB distributor.
Tightening torques for power connections
Screw size Torque
M5 3.5 Nm (2.6 lbf.ft)
M6 9 Nm (6.6 lbf.ft)
M8 20 Nm (14.8 lbf.ft)
M10 40 Nm (29.5 lbf.ft)
M12 70 Nm (52 lbf.ft)
M16 180 Nm (133 lbf.ft)
Applicable standards
The drive complies with the following standards. The compliance with the European Low
Voltage Directive is verified according to standards EN 50178 and EN 60204-1.
• EN 50178 (1997)
Electronic equipment for use in power installations.
• EN 60204-1 (1997)
Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance:
The final assembler of the machine is responsible for installing
- an emergency-stop device
- a supply disconnecting device.
• EN 60529: 1991 (IEC 529)
Degrees of protection provided by enclosures (IP code).
• IEC 60664-1 (1992)
Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
requirements and tests.
• EN 61800-3 (1996) +
Amendment A11 (2000)
EMC product standard including specific test methods
• UL 508C
UL Standard for Safety, Power Conversion Equipment, second edition
• CSA C22.2 No. 14-95
Industrial control equipment
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for ACS800-07-0610-3
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 7: ...Update Notice 3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Update Notice 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...