Update Notice
2
NEW (page 37): Type code
The table below contains the new option code definition for the Safe torque off
function.
NEW (page 61): Emergency stop
Note:
If you add or modify the wiring in the drive safety circuits, ensure that the
appropriate standards (e.g. IEC 61800-5-1, EN 62061, EN/ISO 13849-1 and -2) and
the ABB guidelines are met. After making the changes, verify the operation of the
safety function by testing it.
NEW (page 61): Safe torque off
The drive supports the Safe torque off (STO) function according to standards
EN 61800-5-2:2007; EN/ISO 13849-1:2008, IEC 61508, and EN 62061:2005. The
function also corresponds to an uncontrolled stop in accordance with category 0 of
EN 60204-1 and prevention of unexpected start-up of EN 1037.
The STO may be used where power removal is required to prevent an unexpected
start. The function disables the control voltage of the power semiconductors of the
drive output stage, thus preventing the inverter from generating the voltage required
to rotate the motor (see the diagram below). By using this function, short-time
operations (like cleaning) and/or maintenance work on non-electrical parts of the
machinery can be performed without switching off the power supply to the drive.
Code
Description
+Q968
Safe torque off (STO) with a safety relay
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for ACS800-07-0610-3
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 7: ...Update Notice 3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Update Notice 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...