Technical data
124
Motor connection
Voltage (
U
2
)
0 to
U
1
,
3-phase symmetrical,
U
max
at the field weakening point
Frequency
DTC mode: 0 to 3.2 ×
f
FWP
. Maximum frequency 300 Hz.
f
FWP
=
where
f
FWP
= frequency at field weakening point;
U
Nmains
= mains (input power) voltage;
U
Nmotor
= rated motor voltage;
f
Nmotor
= rated motor frequency
Frequency resolution
0.01 Hz
Current
See section
Ratings.
Power limit
2 ×
P
hd
. After approximately 2 minutes at 2 ×
P
hd
, the limit is set at
P
cont.max
.
Field weakening point
8 to 300 Hz
Switching frequency
2 kHz (average)
Motor cable lead-throughs
3 × Ø60 mm at each inverter module (units without common motor terminal cubicle)
Units with common motor terminal cubicle: See the chapter
Dimensions
.
U
Nmains
U
Nmotor
·
f
Nmotor