Hardware description
31
Digital input and relay output terminals
The DSU can be controlled through two control interfaces: local and remote. The
operation switches placed on the cabinet door are connected to the local control
interface. The remote control interface can be used in parallel when control by other
external devices is needed.
DSSB board terminals
1)
After the power switch-on, the DSU first charges the contactor control
capacitors (~ 3 s at first start) and checks the fault status. DSU starts rectifying
only after the contactors are closed by the START input.
2)
These DSSB board terminals are wired to a separate terminal block to which
the user connections are to be made. See the circuit diagrams delivered with the
unit.
X10 Local digital inputs
1
START
0 -> 1: DSU closes main contactors and starts rectifying.
Note:
Local ON input must be switched on.
2
ON
1: DSU is rectifying.
1)
0: DSU stops rectifying and opens
contactors.
3
+24 V
+24 VDC
4
RESET
0 -> 1: Reset
5
RESET LED Ground for reset button LED
6
+24 V
+24 VDC
X5
Remote digital inputs
2)
1-2
ON
1: DSU is rectifying.
1)
0: DSU stops rectifying and opens
contactors.
Note:
If start command was given through local
START input, DSU stops only after local ON input is
switched off.
3-4
START
0 -> 1: DSU closes main contactors and starts rectifying.
Note:
Local and remote ON inputs must be switched on.
5-6
RESET
0 -> 1: Reset
7-8
EXT.FAULT 1: External fault. DSU trips. 0: No external fault.
X6
Relay outputs
2)
1-2
RO1
Off: Fault
3
-
4-5
RO2
On: Running
X7
Relay outputs
2)
1-2
RO3
Overtemperature warning
3
-
4-5
RO4
Off: Earth (ground) fault detected
6
-
7-8
RO5
Off: Emergency stop acknowledgement to inverter
0
1
ST
1
2
3
4
START
1
0
3
4
1
2
1
0
13
14
X1
X2
S11
S11
S21
S21
13
14
X1
X2
Digital input data
Input voltage: “1” = 15…48 VDC or
15…230 VAC. All inputs must be of the
same type (AC or DC).
Internal connection:
DI
Relay output data
Contact rating:
230 VAC / 1 A continuous
Internal connection:
RO
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for ACS800-07-0610-3
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 7: ...Update Notice 3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Update Notice 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...