Mechanical installation
51
Miscellaneous
Cable duct in the floor below the cabinet
A cable duct can be constructed below the 400 mm wide middle part of the cabinet.
The cabinet weight lies on the two 100 mm wide transverse sections which the floor
must carry.
Viewed from above
Side view
This area can be used for a
cable duct
With heavy
cabinets support
the structural C-
sections from
below.
Prevent the cooling air flow
from the cable duct to the
cabinet by bottom plates.
To ensure the degree of
protection for the cabinet
use the original bottom
plates delivered with the
unit. With user-defined
cable entries, take care of
the degree of protection, fire
protection and EMC
compliance.
Cables