![background image](http://html1.mh-extra.com/html/abb/acs800-07-0610-3/acs800-07-0610-3_hardware-manual_3428312052.webp)
Mechanical installation
46
Holes inside the cabinet
The cabinet can be fastened to the floor using the fastening holes inside the cabinet,
if they are accessible. The recommended maximum distance between the fastening
points is 800 mm (31.5”).
If there is not enough working space behind the cabinet for mounting, replace the
lifting lugs at the top with L-brackets (not included) and fasten the top of the cabinet
to the wall.
Fastening holes inside the
cabinet (arrowed)
≈
0.5
IP 54
IP 20...42
25 mm (0.9
85”)
Added width:
Side panels of the cabinet: 15 mm (0.6”)
Back panel of the cabinet: 10 mm (0.4”)
Gap between cubicles (mm):
Distances between fastening holes
Bolt size: M10 to M12 (3/8” to 1/2”).
Cubicle
Width
Distance between holes
300
150 mm (5.9”)
400
250 (9.85”)
600
450 (17.7”)
700
550 (21.65”)
800
650 (25.6”)
Outer
Ø31 mm (1.22”)
Fastening the cabinet at the top with
L-brackets (side view)
L-bracket
M16 screw
Cabinet top
(0.02”)
≈
1
(0.04”)