Technical data
131
Second environment
The drive complies with the limits of IEC 61800-3 with the following provisions:
1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In
some cases, the natural suppression in transformers and cables is sufficient. If in doubt, the supply
transformer with static screening between the primary and secondary windings is strongly
recommended.
2. The drive is installed according to the instructions given in the drive manuals.
3. The motor and control cables used are selected as specified in the drive manuals.
Low voltage
Equipment
Low voltage
Equipment
Equipment
(victim)
Supply transformer
Medium voltage network
Static screen
Point of measurement
Drive
Neighbouring network