Mechanical installation
50
DC busbars
The DC busbar connection is shown below.
PE busbar
The PE busbar runs continuously through the line-up near the floor at the back. The
connection is shown below. No separate nuts are needed.
Tighten the bolts to
55–70 Nm (40–50 ft.-lbs.)
Side view of single busbar connection
Joint pieces
1
1
1
1
1
1
Shipping split A
Shipping split B
Top view
PE busbar
Tighten the screws to
55–70 Nm (40–50 ft.-lbs.)