Planning the electrical installation
69
A diagram of the cable routing is below.
Control cable ducts
90 °
min 500 mm (20 in.)
Motor cable
Input power cable
Control cables
min 200 mm (8 in.)
min 300 mm (12 in.)
Motor cable
Power cable
Drive
230/120 V
24 V
24 V 230/120 V
Lead 24 V and 230/120 V control
cables in separate ducts inside
the cabinet.
Not allowed unless the 24 V
cable is insulated for 230/120 V
or insulated with insulation
sleeving for 230/120 V.