Maintenance
106
Checking and replacing the air filters
1. Read and repeat the steps in
Safety instructions
above.
2. Open the cabinet doors.
3. Check the air filters and replace if necessary (see
Technical data
for the correct
filter types). The inlet (door) filters can be accessed by removing the fastener(s) at
the top of the grille, then lifting the grille and pulling it away from the door. The
outlet (roof) filter in IP54 units has a similar mechanism.
4. Check the cleanliness of the cabinet. Clean the interior of the cabinet if necessary
using a soft brush and a vacuum cleaner.
5. Close the cabinet doors.
Power connections
1. Read and repeat the steps in section
Safety instructions
above.
2. Open the cabinet doors.
3. Extract one supply or inverter module from the cabinet as described in the
connection procedures in the chapter
Electrical installation
.
4. Check the tightness of the cable connections at the quick connector. Use the
tightening torque table in
Technical data
.
5. Clean all contact surfaces of the quick connector and apply a layer of suitable joint
compound (e.g. Isoflex
®
Topas NB 52 from Klüber Lubrication) onto them.
6. Re-insert the supply/inverter module.
7. Repeat steps 3 to 6 for all remaining supply and inverter modules.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for ACS800-07-0610-3
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 7: ...Update Notice 3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Update Notice 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...