![background image](http://html1.mh-extra.com/html/abb/acs800-07-0610-3/acs800-07-0610-3_hardware-manual_3428312132.webp)
Technical data
126
Cooling
Method
Internal fans, flow direction from bottom to top
Filter material
Inlet (door)
Outlet (roof)
IP22/IP42 units
Luftfilter airTex G150
–
IP54 units
Luftfilter airComp 300-50
Luftfilter airTex G150
Free space around the unit
See chapter
Mechanical installation
.
Cooling air flow
See
Ratings.
Degrees of protection
IP21; IP22; IP42; IP54, IP54R (with air outlet duct)
Ambient conditions
Environmental limits for the drive are given below. The drive must be used in a heated,
indoor controlled environment.
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 4000 m (13123 ft) above
sea level [above 1000 m
(3281 ft), see section
Derating
]
-
-
Air temperature
-15 to +50 °C (5 to 122 °F),
no frost allowed.
See section
Derating
.
-40 to +70 °C (-40 to +158°F) -40 to +70 °C (-40 to +158°F)
Relative humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels
(IEC 60721-3-3, IEC 60721-3-
2, IEC 60721-3-1)
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Atmospheric pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
(IEC 60068-2)
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
2
(49 ft/s
2
)
(9 to 200 Hz) sinusoidal
Shock
(IEC 60068-2-29)
Not allowed
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Free fall
Not allowed
100 mm (4 in.) for weight
over 100 kg (220 lb)
100 mm (4 in.) for weight
over 100 kg (220 lb)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for ACS800-07-0610-3
Page 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 7: ...Update Notice 3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Update Notice 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...