06 ELECTRICAL INSTALLATION
3BHS842007 E01 REV C
ACS6080
USER MANUAL
150/238
• Connect the individual shields and the overall shield (if present) of
encoder cables to the separate shield grounding point (Fig. 6-33).
IMPORTANT!
DO NOT connect the shields to the terminals of
the interface.
• Different-sized ground clamps are supplied.
Figure 6-33 Shield grounding for encoder cable
6.8.7
Routing cables in an EXU cabinet
This section applies to a stand-alone EXU.
6.8.7.1
Auxiliary power and control cables
1.
Enter the cables through a free hole of the EMC plate.
2.
On the length of cable that passes through the cable transit, prepare
the cable according to the following instructions:
• Cable entries with EMC plates:
“6.8.4 Preparing cables for EMC
• Cable entries with cable glands:
“6.8.3 Preparing cables for cable
Note:
Materials for cable fitting, EMC requirements and sealing are not
supplied for undrilled plates.
(1) Exposed cable shielding
(2) Ground clamp (SK8)
(3) Ground clamp (SK14)
(4) Ground clamp
(5) Encoder
1
2
3
4
5