8.10.3
Starting the drive locally
1.
Set the control panel to local mode with the
Loc/Rem
key.
2.
If the
EMERGENCY-OFF RESET
push button on the COU is flashing,
press the push button to cancel flashing.
Note:
Each time the auxiliary voltage is switched off and on again, the
emergency-off safety relay of the drive is actuated and lets the
EMERGENCY-OFF RESET
pushbutton flash. The
EMERGENCY-OFF
RESET
push button also flashes if the
EMERGENCY-OFF
push button
on the control compartment door, or any other
EMERGENCY-OFF
push
button linked to the drive, is pressed. If the
EMERGENCY-OFF RESET
push button continuous flashing, verify that there is no emergency-off
command active. See “8.11.2 Stopping the drive with the emergency-
off function” on page 181
3.
Check that no alarm or fault messages are displayed on the
control panel.
• When a fault message is displayed on the control panel, reset
the fault.
• If a fault cannot be reset, the responsible personnel must rectify it.
• (Drives with an ARU) When faults are present and the drive is ready,
the INU is “Ready to switch on”.
Loc/Rem
?
Start
Stop
Options
23:58
Menu
Local
ACS6080
1400.0 Rpm
Motor speed
Rpm
Motor current
A
Flow rate
m
3
/s
1400.0
28.8
10.9