03 POWER ELECTRONICS AND CABINET FEATURES
Transportation
Small drives are shipped as one unit. Larger drives are shipped in separate
transport units. All transport units are fitted with lifting lugs for a crane
that must be used to position the units.
Safety labels
Safety labels are attached to the drive doors to alert personnel of
potential hazards when working on the drive.
The standard language of the labels is English; however, other languages
can be ordered. The label design is based on the relevant ANSI and ISO
standards.
Note:
For more information, see “2.3 Product safety labels” on page 40.
3.6
Door locking system
For more information on the door locking system, including grounding
switches, locking bars, and safety switches, see “8.6 EXU control panel”
on page 168.
3.7
Arc resistant design
The optional “Arc Resistant Design” provides the drive with arc fault
protection (see Table 3-7) in accordance with IEC 62477-2.
3.7.1
Internal arc classification
The arc fault rating, which is based on arc fault tests, is on the label
underneath the drive rating plate of the drive.
Table 3-7 ABB arc resistant classes
ABB class
Description
Class I
Protection based on arc prevention (NOT certified according to
IEC 62477-2)
Class II
Protection based on arc resistant cabinet structure
(1)
(1)
IAC certified by 3
rd
body according to IEC 62477-2
Class III
Protection based on external arc fault limitation and elimination.
HV fuses are applied externally to limit the arc fault current
(1)
Class IV
Fast arc detection and elimination
(1)