06 ELECTRICAL INSTALLATION
3BHS842007 E01 REV C
ACS6080
USER MANUAL
146/238
5.
If the outer cable screen is conductive, remove the cable insulation at
the point of entry (1 in Fig. 6-28).
If the outer cable screen is non-conductive:
1.
Cut open the cable screen in the middle of the stripped area
(1 in Fig. 6-28).
2.
Pull the cable screen ends over the cable insulation to turn the
conductive side inside out (2 in Fig. 6-28).
3.
Connect the screens ends with a continuous conducting foil
(3 in Fig. 6-28).
Figure 6-28 Preparing the screens of control cables for EMC plates
(1) Cable screen
(2) Cable screen ends
(3) Conductive foil
1
2
2
3
3