3BHS842007 E01 REV C
ACS6080
USER MANUAL
139/238
06 ELECTRICAL INSTALLATION
3.
Slide the grommet onto the cable and ensure that the grommet fits
tightly to prevent water from entering the cabinet.
Note:
If cables are entered through the cabinet floor, the grommets
can be discarded.
4.
If necessary, remove the entry plate and push the cable through the
entry holes.
5.
Prepare standard cables according to Fig. 6-20.
6.
Prepare EXU cables according to Fig. 6-20.
The orientation of the EMC plates in both scenarios is the same for top
and bottom cable entries, ie, the sealing grommets face upwards.
Figure 6-20 Preparing cables for EMC plates: (A) cables with an outer screen or
shield, (B) cables without an outer screen or shield or (C) cables in an
EXU cabinet
(1) Grommet
(2) EMC sleeve
(3) Cable tie
(4) Heat-shrinkable termination
(5) Outer cable sheath
(6) Entry plate
(7) Conductor insulation removed to
expose cable shield
(8) Cable screen extension to connect
to the PE busbar
(9) Cable clamp
A
B
C
1
1
2
2
3
4
5
5
6
6
7
7
8
9