3BHS842007 E01 REV C
ACS6080
USER MANUAL
129/238
06 ELECTRICAL INSTALLATION
4.
Wind up the excess cable lengths to the reeling device in the REB.
NOTICE
These cables are only available in standard lengths and cannot
be cut or extended. The excess cable must be wound up in coils with a
diameter of at least 100 mm.
6.5
Cable entry systems
Depending on your drive configuration, one or a combination of the
following cable entry systems might be used on a cabinet for top and/or
bottom cable entry:
• “6.5.1 Frames with type 1 sealing modules” on page 129
• “6.5.2 Frame with type 2 sealing modules” on page 131
• “6.5.3 Plates with cable glands” on page 131
• “6.5.4 EMC plates with sealing grommets” on page 132
Note:
For information on the location and the dimensions of the cable
entry, see “Appendix C – Mechanical drawings”.
6.5.1
Frames with type 1 sealing modules
Figure 6-9 Cable entry with type 1 sealing modules
(1) Compression wedge
(2) Sealing module (RM120)
(3) Cable entry frame
Usage
• Power cables
• Ground cables
• Equipotential bonding conductors
Included in delivery
• Cable entry frame
Not included in
delivery
• Sealing modules
• Accessories
• Tools
1
2
3