3BHS842007 E01 REV C
ACS6080
USER MANUAL
149/238
06 ELECTRICAL INSTALLATION
3.
Route the cables to their destination.
Figure 6-32 Cable routing in 1000 mm COU (A) and 600 mm COU (B)
6.8.6.1
Connecting the cables
For information on the encoders, see the relevant user manual:
• Absolute encoder (SSI) and incremental encoder (TTL):
Encoder Interface FEN-11 user manual" (3AFE68784841)
• Incremental encoder (HTL):
"HTL Encoder Interface FEN-31 user
Conductors
• If a twisted pair cable is used, leave the unshielded cable ends
twisted until they reach the terminals.
• Leave unshielded conductor ends as short as possible (not longer
than 50 mm).
Cable shields
• Connect the shield of serial communications cables to the
fieldbus adapter.
A
B