09 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS842007 E01 REV C
ACS6080
USER MANUAL
234/238
5.
Pull the fan unit out of the cabinet.
CAUTION!
To prevent the fan from falling onto you, put a support (ie, a
box) underneath.
6.
Install the new fan in reverse order of removal.
9.4.19
Replacing the air-to-water heat exchanger of the EXU
1.
Switch off the miniature circuit breaker of the heat exchanger.
Note:
To identify the miniature circuit breaker, see “Appendix D –
Wiring diagrams”.
2.
Close valves V30 and V31 in the water-cooling unit.
3.
Disconnect the hose from valve V30 to drain the WCU.
NOTICE
Expect approximately 5 liters of water.
4.
Unscrew the top plate.