06 ELECTRICAL INSTALLATION
3BHS842007 E01 REV C
ACS6080
USER MANUAL
122/238
6.2
Cable requirements
Power, auxiliary and control cables have different requirements.
6.2.1
Power cables
For information on the requirements for power cables, ground cable and
equipotential bonding conductor, see:
• "Power cable specification" (3BHS125090 E01)
• "Power cables engineering guideline" (3BHS542290 E01)
6.2.2
Auxiliary and control cables
Note:
For information on the requirements for the auxiliary power cable
and the control cables, see "Auxiliary power and control cables guideline"
(3BHS813742 E01).
6.2.3
Synchronization cables
Synchronization cables are used in drives with an ARU. A shielded, 3-phase
cable without neutral wire is required for the supply voltage of the
synchronization transformer.
▲
NOTICE
Risk of false signals!
• DO NOT lay control cables in parallel to the power supply cables.
• If this cannot be avoided, a minimum distance of
30 cm
must be
maintained between control and power supply cables.
• Cross control and power supply cables at an angle of 90°