3BHS842007 E01 REV C
ACS6080
USER MANUAL
175/238
08 OPERATION
Tripped
8.9.1
Start sequence of the drive
Indicates that a fault condition has occurred that requires a
shutdown of the drive. The status message always alternates with
the specific fault message. The type of shutdown depends on the
fault class the fault condition is assigned to in the drive software.
1) Not ready to switch on
2) ARU Ready on
• Only drives with an ARU (see the next step, Ready to switch
on, for the conditions)
3) Ready to switch on
• Auxiliary power supply on
• Doors of medium voltage units closed and locked
• Drive is not grounded
• No emergency-off
• No fault
• WCU ready
4) On command
5) Charging
• DC link charges
• MCB closes
• Cooling system switches on
6) ARU Ready ref
• Only in drives with an ARU
7) Ready run
• INU starts magnetizing (only in drives with an ARU)
• INU starts to modulate
8) Start command
9) Ready ref
10) Operation