09 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS842007 E01 REV C
ACS6080
USER MANUAL
194/238
9.4.2
De-energizing and grounding the drive
The following section describes how to de-energize the drive using the
local operator panel of the drive. If the drive is controlled from remote,
follow the established shutdown procedures.
Procedure
1.
Set the control panel to local mode with the location key (Loc/Rem).
2.
Press the STOP key ( ) on the control panel to stop the motor.
The motor stops according to the preset stop function. When the
motor has reached zero speed, the drive is in “Ready run.
3.
Press the
SUPPLY OFF
push button to disconnect the drive from the
main power supply.
▲
NOTICE
Risk of component damage!
Foreign matter and particularly metallic dust can cause failure and
damage when the drive is energized! Ensure that foreign matter cannot
enter the cabinet.
• Close the doors and cover openings completely when work
is discontinued.
• Retrieve any foreign matter which accidentally dropped into
the cabinet.