09 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS842007 E01 REV C
ACS6080
USER MANUAL
214/238
3.
Remove the bolts (4) on each side of the phase module.
Figure 9-22 Phase module removal
4.
Place the lifting table in front of the phase module.
5.
Adjust the height of the table so that it is level with the rails on the
underside of the phase module.
6.
Pull the phase module onto the table.
CAUTION
A phase module weighs approximately
190 kg
. When pulling
out the phase module, make sure that the disconnected water hoses,
optical fibers and power supply leads are out of the way.
(1) 1/2”
(2) 80 mm
(3) 17 mm
(4) Location of bolts to remove
1
2
3
4
4
4
4