Actual signals and parameters 241
4018 ACT1
MINIMUM
Sets the minimum value for ACT1.
Scales the source signal used as the actual value ACT1
(defined by parameter
). For parameter
values 6 (
) and 7 (
scaling is not done.
A = Normal; B = Inversion (ACT1 minimum > ACT1
maximum)
0%
-1000…1000% Value in percent
1 = 1%
4019 ACT1
MAXIMUM
Defines the maximum value for variable ACT1 if an analog
input is selected as a source for ACT1. See parameter
. The minimum (
) and
maximum settings of ACT1 define how the voltage/current
signal received from the measuring device is converted to a
percentage value used by the process PID controller.
See parameter
.
100%
-1000…1000% Value in percent
1 = 1%
4020 ACT2
MINIMUM
See parameter
.
0%
-1000…1000% See parameter
1 = 1%
4021 ACT2
MAXIMUM
See parameter
.
100%
-1000…1000% See parameter
1 = 1%
4022 SLEEP
SELECTION
Activates the sleep function and selects the source for the
activation input. See section
Sleep function for the process
.
NOT SEL
No sleep function selected
0
DI1
The function is activated/deactivated through digital input
DI1.1 = activation, 0 = deactivation.
The internal sleep criteria set by parameters
are not effective.
The sleep start and stop delay parameters
are effective.
1
DI2
See selection
.
2
All parameters
No.
Name/Value
Description
Def/FbEq
Par
Source
Source min.
Source max.
1
Analog input 1 1301 MINIMUM AI1 1302 MAXIMUM AI1
2
Analog input 2 1304 MINIMUM AI2 1305 MAXIMUM AI2
3
Current
0
2
·
nominal current
4
Torque
-2
·
nominal torque
2
·
nominal torque
5
Power
-2
·
nominal power
2
·
nominal power
Source min.
ACT1 (%)
ACT1 (%)
A
B
Source max.
Source signal
Source min.
Source max.
Source signal