272 Actual signals and parameters
8118 AUTOCHNG
INTERV
Controls operation of the Autochange function and sets the
interval between changes.
The Autochange time interval only applies to the time when
the speed regulated motor is running.
See parameter
for an overview of
the Autochange function.
The drive always coasts to stop when Autochange is
performed. Autochange enabled requires parameter
> 0.
WARNING!
When enabled, the Autochange function
requires the interlocks (
> 0)
enabled. During Autochange the power output is interrupted
and the drive coasts to stop, preventing damage to the
contacts.
-0.1 = TEST
MODE
0.0 = NOT SEL
0.1…336.0 h
-0.1: Test mode. Forces the interval to value 36…48 s.
0.0: Disables the Autochange function.
0.1…336 h: The operating time interval (the time when the
start signal is on) between automatic motor changes.
1 = 0.1 h
All parameters
No.
Name/Value
Description
Def/FbEq
Relay logic
PFC with Autochange mode