150 Program features
User load curve
The user can specify a load curve (motor torque as a function of frequency) for
supervision. The curve is defined by five points. Supervision can be set for the torque
dropping below the underload curve, exceeding the overload curve, or both.
A fault is generated if the torque has been out of the allowed area for longer than the
user-defined time limit. An alarm is generated if the torque has been out of the
allowed area for longer than the half of the user-defined time limit.
Settings
Diagnostics
Parameter
Additional information
Group
User load curve settings
Actual signal
Additional information
Motor torque
Alarm
Out of allowed area for longer than half of the defined
time limit
Fault
Out of allowed area for longer than the defined time
limit
Incorrect user load curve parameter setting
or
>
or
or
or
)
Overload area
Underload area
Allowed operating area
Motor torque
(%)
Output
frequency
(Hz)
Freq. 2
Freq. 1
Freq. 3 Freq. 4
Freq. 5
Torque
high 1
Torque
high 2
Torque
high 3
Torque
low 1
Torque
low 2
Torque
low 3
Torque
high 4
Torque
low 4
Torque
high 5
Torque
low 5